Troubleshooting

9.1.2 Minor Fault Detection

- 6

9.1.2 Minor Fault Detection

Minor faults are a type of Inverter protection function that do not operate the fault contact output and are auto-
matically returned to their original status once the cause of the minor fault has been removed.

The Digital Operator display blinks and the minor fault is output from the multi-function outputs (H2-01 to
H2-03).

Take appropriate countermeasures according to the table below.

Table

9.2

Minor Fault Displays and Processing

Minor fault display

Meaning

Probable causes

Corrective Actions

EF (blinking)

External Fault

Forward/Reverse Run Commands
Input Together

Both the forward and reverse run
commands have been ON for more
than 0.5 s.

-- --

Check the sequence of the forward
and reverse run commands.

Since the rotational direction is un-

known, the motor will be deceler-
ated to a stop when this minor
fault occurs.

UV (blinking)

DC Bus Undervolt

Main Circuit Undervoltage

The following conditions occurred
when there was no Run signal.

S The main circuit DC voltage was

below the undervoltage detection
level (L2-05).

S The surge current limiting contac-

tor opened.

S The control power supply voltage

when below the CUV level.

See causes for UV1 UV2 and UV3
faults.

See corrective actions for
UV1 UV2 and UV3 faults.

OV (blinking)

Overvoltage

Main Circuit Overvoltage

The main circuit DC voltage exceed-
ed the overvoltage detection level.

200 V class: Approx. 400 V
400 V class: Approx. 800 V

The power supply voltage is too high.

Decrease the voltage so it’s within
specifications.

Cooling Fin Overheating

The ambient temperature is too high.

Install a cooling unit.

OH (blinking)

H

i k O

The temperature of the Inverter’s
cooling fins exceeded the setting in

There is a heat source nearby.

Remove the heat source.

Heatsink Over tmp

cooling fins exceeded the setting in
L8-02.

The Inverter cooling fan has stopped.

Replace the cooling fan. (Contact
your Yaskawa representative.)

OH2 (blinking)

Over Heat 2

Inverter Overheating Pre-alarm

An OH2 alarm signal (Inverter over-
heating alarm signal) was input from
a multi-function input.

-- --

Clear the multi-function input’s over-
heating alarm input.

OL3 (blinking)

Overtorque Det 1

Overtorque 1

There has been a current greater than
the setting in L6-02 for longer than
the setting in L6-03.

-- --

S Make sure that the settings in L6-02

and L6-03 are appropriate.

S Check the mechanical system and

correct the cause of the overtorque.

OL4 (blinking)

Overtorque Det 2

Overtorque 2

There has been a current greater than
the setting in L6-05 for longer than
the setting in L6-06.

-- --

S Make sure that the current setting in

L6-05 and time setting in L6-06 are
appropriate.

S Check the mechanical system and

correct the cause of the overtorque.

Overspeed

The speed has been greater than the

i

i F1 08 f

l

h

h

Overshooting/undershooting are oc-
curring.

Adjust the gain again.

OS (blinking)

Over speed

e speed as bee g eate t a t e

setting in F1-08 for longer than the
setting in F1-09.

The reference speed is too high.

Check the reference circuit and refer-
ence gain.

O e speed

The settings in F1-08 and F1-09
aren’t appropriate.

Check the settings in F1-08 and
F1-09.

PGO (blinking)

The PG is disconnected.

There is a break in the PG wiring.

Fix the broken/disconnected wiring.

PGO (blinking)

PG open

The Inverter is outputting a frequen-
cy, but PG pulses aren’t being input.

The PG is wired incorrectly.

Fix the wiring.

PG open

cy, but PG pulses aren t being input.

Power isn’t being supplied to the PG.

Supply power to the PG properly.

Excessive Speed Deviation

The load is too large.

Reduce the load.

DEV (blinking)

The speed deviation has been greater
than the setting in F1-10 for longer
than the setting in F1-11.

The acceleration time and decelera-
tion time are too short.

Lengthen the acceleration time and
deceleration time.

(

g)

Speed Deviation

than the setting in F1-11.

The load is locked.

Check the mechanical system.

The settings in F1-10 and F1-11
aren’t appropriate.

Check the settings in F1-10 and
F1-11.