Caution, 7 autotuning mode – Yaskawa VS-626 MC5 User Manual

Page 92

Advertising
background image

4.2Modes

- 29

4.2.7 Autotuning Mode

CAUTION

D

Disconnect the load (machine, device) from the motor before autotuning.

The motor may turn, possibly resulting in injury or damage to equipment. Also, motor constants cannot be
correctly set with the motor attached to a load.

Autotuning automatically tunes and sets the required motor constants when operating in the open-loop or
flux vector control modes. Always perform autotuning before starting operation.

When the rated voltage, rated current, rated frequency, and number of poles listed on the motor nameplate
have been input and the RUN Key is pressed, the motor constants calculated from these values will be writ-
ten to E1-04 through E2-09 automatically.

When motor cannot be disconnected from the load, motor constants can be set by calculation.
Contact your YASKAWA representatives for details.

The Inverter’s autotuning function automatically determines the motor constants, while a servo system’s
autotuning function determines the size of a load, so these autotuning functions are fundamentally differ-
ent.

Autotuning Procedure

Step

Key Sequence

Digital Operator Display

Remarks

1

MENU

MC5

Main Menu

Operation

2

press 3 times.

MC5

Main Menu

Autotuning

3

DATA

ENTER

Rated Voltage (see note)

200

.

0 VAC

4

DATA

ENTER

Rated Voltage

200

.

0 VAC

The leading digit blinks.
When Increment Key is pressed,
blinking value increases. When
Decrement Key is pressed, blinking
value decreases.

5

RESET

Rated Voltage

200

.

0 VAC

The digit to be set moves to the right
and blinks. Follow the above proce-
dures as outlined in step 4.

6

DATA

ENTER

Entry Accepted

After selecting values for steps 4 and
5, press DATA/ENTER Key.
The Operator display is as shown on
the left. The value is written-in.

Rated Voltage

200

.

0 VAC

After a few seconds, the Operator dis-
play is as shown on the left.

7

Rated Current

1

.

90 A

8

RESET

DATA

ENTER

DATA

ENTER

Press the keys as in steps 4, 5, 6 of
rated voltage setting.

9

Rated Frequency

60

.

0 HZ

10

RESET

DATA

ENTER

DATA

ENTER

Press the keys as in steps 4, 5, 6 of
rated voltage setting.

11

Rated Speed

1750 RPM

12

RESET

DATA

ENTER

DATA

ENTER

Press the keys as in steps 4, 5, 6 of
rated voltage setting.

Note Rated voltage for vector control motors is approx. 10 to 20% lower than general--purpose

motors. Verify motor voltage listed on the nameplate or the test report before use.

4

A

EXAMPLE

"

Advertising