User Constants

8.2.7 Protection Constants: L

- 30

Constant

Number

Page

Control Methods

Change

during

Opera-

tion

Factory

Setting

Setting

Range

Description

Name

Constant

Number

Page

Flux Vector

Open Loop

Vector

Change

during

Opera-

tion

Factory

Setting

Setting

Range

Description

Display

L8-17

Carrier frequency re-
duction selection

0: No carrier frequency reduction
1: With carrier frequency reduc-

tion

2: For factory adjustments
3. For factory adjustments

If the metallic noise (carrier

i )

t d f

th

t

0 to 3

1

A

- 59

L8 17

L--Spd IGBT Prtct

(

noise) generated from the motor
at low speeds (less than 6 Hz)
becomes a problem, set L8--17 to
0 and L8--19 to 1.
However, do not set L8--17 or
L8--19 to 0 when using open--
loop vector control.

0 to 3

1

A

- 59

L8-19

OL2 characteristics
seleciton at low
speeds

0: OL2 characteristics at low

speeds disabled.

1: OL2 characteristics at low

speeds enabled.

If using OL2 to trip at low speeds

(less than 6 Hz) even though the
load is light, set L8--17 to 1 and
L8--19 to 0

0 1

0

A

A

- 59

OL2 Chara @ L--Spd

L8--19 to 0.
However, do not set L8--17 or
L8--19 to 0 when using open--
loop vector control.
Do not set L8--19 to when using
a 400 V class (185 to 300 kW)
Inverter.