6.1.2 Frequency Reference Settings: b1-01, H3-01, H3-08, H3-09

- 4

6.1.2 Frequency Reference Settings: b1-01, H3-01, H3-08, H3-09

These settings are required when inputting analog voltage or current signals from the control circuit termi-
nals.

J

Frequency Reference Selection: b1-01

D

Constant b1-01 is used to select the reference source.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

b1-01

Reference selection

0 to 3

--

1

Q

Q

D

Settings

Setting

Reference source

0

Digital Operator

1

Control circuit terminals (analog inputs)

2

Transmission

3

Optional Card

D

The frequency reference is input from the control circuit terminals (external terminals), so set b1-01
to 1.

J

Frequency Reference (Voltage), Terminal 13 Signal Level: H3-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

H3-01

Signal level selection
(terminal 13)

0 1

--

0

B

B

D

The frequency reference (voltage) is valid when constant b1-01 has been set to 1.

D

Set the voltage range for the frequency reference (voltage) signal.

D

Settings

Setting

Function

0

0 to 10 VDC input [11--bit + polarity (positive/negative) input]

1

--10 to 10 VDC input
(A negative voltage is a reference for reverse rotation.)

J

Frequency Reference (Current), Terminal 14 Signal Level: H3-09, H3-08

D

Set terminal 14 to a frequency reference with constant H3-09 to use terminal 14 as the frequency refer-
ence terminal.

D

The frequency reference setting is 1F.

Function Selection: H3-09

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

H3-09

Multi-function analog
input (terminal 14)

1 to 1F

--

1F

A

A

D

After setting constant H3-09, set terminal 14 signal level with H3-08.

Signal Level: H3-08

D

The frequency reference (current) is valid when constant b1-01 has been set to 1.

D

Set the signal level for the frequency reference (current).

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

H3-08

Signal level selection
(terminal 14)

0

2

--

2

A

A

6