Flux Vector Control

- 27

6.3.3 Autotuning for general-purpose motors

Autotuning for general purpose motors

CAUTION

D

Do not connect a load to the motor when performing autotuning.

Doing so may result in personal injury or equipment damage.

When motor cannot be disconnected from the load, motor constants can be set by calculation. Contact your
YASKAWA representatives for details.

J

Precautions Before Autotuning

D

The Inverter’s autotuning function automatically determines the motor constants while a servo sys-
tem’s autotuning function determines the size of a load, so these autotuning functions are fundamental-
ly different.

D

If a load is connected when autotuning is performed, not only will incorrect motor constants be re-
corded, but the motor may operate erratically or unexpectedly. Disconnect the load before autotuning.

D

The motor shaft will rotate when autotuning is performed. Confirm safety before starting autotuning.

D

When motor cannot be disconnected from the load, motor constants can be set by calculation. Contact
your YASKAWA representatives for details.

J

Inverter Input Voltage Setting: E1-01

D

Set the Inverter input voltage to match the power supply voltage.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

E1-01

Input voltage setting

155 to 255

(310 to 510)

VAC

200

(400)

Q

Q

D

The voltage settings shown in parentheses are for 400 V class Inverters.

D

This setting is used as the reference value for functions such as the protection functions.

J

Motor Selection (Motor Overheating Protection): E1--02

D

Set the type of motor being used. This setting is a reference for overheating protection functions.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

E1-02

Motor selection (motor
overheating protection)

0 to 2

--

0

Q

Q

D

Settings

Setting

Function

0

Standard motor (general--purpose motor)

1

Special motor (inverter--exclusive motor)

2

Special motor (vector--exclusive motor)