Yaskawa VS-626 MC5 User Manual

Page 225

Advertising
background image

8.2

Programming Mode Constants

- 17

8.2.5 Options Constants: F

J

PG Option Setup: F1

Constant

Name

Setting

Factory

Change

during

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

F1-01

PG constant

Sets the number of PG (pulse gen-
erator or encoder) pulses.

0 to

600

Q



F1-01

PG Pulse/Rev

erator or encoder) pulses.

Sets the number of pulses per mo-

tor revolution.

0 to

60000

600

Q

Š 

F1-02

Operation selection at
PG open circuit

Sets the PG disconnection stopping
method.
0: Ramp to stop (Deceleration stop

using deceleration time 1,
C1-02.)

1: Coast to stop

0 to 3

1

B

- 23

F1 02

PG Fdbk Loss Sel

1: Coast to stop
2: Fast stop (Emergency stop using

the fast-stop time, C1-09.)

3: Continue operation (PGO is dis-

played, and continues opera-
tion.)

0 to 3

1

B

- 23

F1-03

Operation selection at
overspeed

Sets the stopping method when an
overspeed (os) fault occurs.
0: Ramp to stop (Deceleration stop

using deceleration time 1,
C1-02.)

1: Coast to stop

0 to 3

1

B

- 24

F1 03

PG Overspeed Sel

1: Coast to stop
2: Fast stop (Emergency stop using

the fast-stop time, C1-09.)

3: Continue operation (OS is dis-

played, and continues opera-
tion.)

0 to 3

1

B

- 24

F1-04

Operation selection at
deviation

Sets the stopping method when a
speed deviation (DEV) fault occurs.
0: Ramp to stop (Deceleration stop

using deceleration time 1,
C1-02.)

1: Coast to stop

0 to 3

3

B

- 24

F1 04

PG Deviation Sel

1: Coast to stop
2: Fast stop (Emergency stop using

the fast-stop time, C1-09.)

3: Continue operation (DEV is dis-

played and continues operation.)

0 to 3

3

B

- 24

F1-05

PG rotation

0: Phase A leads with forward run

command. (Phase B leads with
reverse run command.)

0 1

0

B

22

F1-05

PG Rotation Sel

reverse run command.)

1: Phase B leads with forward run

command. (Phase A leads with
reverse run command.)

0 1

0

B

- 22

F1-06

PG division rate (PG
pulse monitor)

Sets the division ratio for the PG
speed control card pulse output.
Division ratio = (1+ n) /m (n=0,1
m=1 to 32)

F1--06 =

1 to 132

1

B

- 23

F1 06

PG Output Ratio

This constant is only effective

when a PG-B2 is used.
The possible division ratio set-
tings are: 1/32

%F1-06%1.

m

n

1 to 132

1

B

- 23

F1-08

Overspeed detection
level

Sets the overspeed detection meth-
od.
Frequencies above that set for

0 to 120

115

A

- 24

F1 08

PG Overspd level

Frequencies above that set for
F1-08 (set as a percentage of the

0 to 120

115

A

- 24

F1-09

Overspeed detection
delay time

F1 08 (set as a percentage of the
maximum output frequency), which
continue to exceed this frequency
for the detection time (F1-09), are

0.0 to

2 0

0.0 *

A

- 24

F1 09

PG Overspd Time

for the detection time (F1-09), are
detected as overspeed faults.

2.0

0.0

A

- 24

*

The setting range will change when the control method is changed. (The values for Open loop vector control is given.)