6.3

Flux Vector Control

- 23

VS-626MC5

Motor

PG (encoder)

Forward

Pulse output

Phase A

Phase B

Phase A

Phase B

Setting: 0

Setting: 1

D

Forward rotation in a typical motor (applicable Yaskawa PG: made by Thermtac):

Forward

The motor output shaft rotates in
the counterclockwise direction
with a forward inverter reference.

Phase A

Phase B

Forward rotation

D

Phase A leading in a typical PG:

Phase A leads when the input axis rotates clockwise.

Phase A

Phase B

Fig

6.9

PG Rotation Direction Setting

J

PG Pulse Output Monitor Division Rate: F1-06

D

This constant is effective only when a PG-B2 PG Control Card is used.

D

It sets the division ratio used when the pulse monitor output is connected to a pulse input device.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

F1-06

PG division rate (PG
pulse monitor)

1 to 132

--

1

B

D

The first digit in the setting (0 or 1) is n and the second two digits (01 to 32) are m. The division ratio
is calculated from n and m with the following equation:

Division ratio

=

( 1

+

n )/m

Setting Ranges

n: 0, 1

m: 1 to 32

F1-06

=

m

n

D

Possible division rate settings are as follows: 1/32

% F1-06 % 1. For example, if the division rate is

1/2 (a setting of “2”), the monitor output will be half of the number of pulses output from the PG.

J

Fault Detection Functions: F1-02 to F1-04, F1-08 to F1-11, F1-14

PG Disconnection Stopping Method: F1-02, F1-14

D

Sets the PG open-circuit detection time and stopping method that is used when a break is detected in
the PG cable (PGO).

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

F1-02

Operation selection at
PG open circuit

0 to 3

--

1

B

F1-14

PG open-circuit detec-
tion time

0.0 to 10.0

s

2.0

A

D

Settings

Setting

Function

0

Deceleration to stop using deceleration time 1 (C1-02).

1

Coast to stop