Basic Operation

6.1.1 Setting the Access Level and Control Method: A1-01, A1-02

- 2

6.1

Common Settings

This section describes the constants that are used with all of the control methods.

6.1.1 Setting the Access Level and Control Method: A1-01, A1-02

J

Constant Access Level: A1-01

D

Select the constant access level. This level determines which constants can be accessed and changed.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

A1-01

Constant access level

0 to 4

--

2 (Q)

Q

Q

D

Access Level Settings

Setting

Name

Function

0

Operation Only

Allows the operation mode and initialize mode to be displayed or
changed. Use this setting to prevent constant settings from being
changed.

1

User Program

Allows only the user-selected constants (up to 32) to be displayed or
changed. Set the desired constants as “User Parameters” in constants
A2-01 through A2-32.

2

Quick-Start

Allows the constants required to start the Inverter (about 25) to be
displayed or changed.

3

Basic

Allows the commonly used constants to be displayed or changed.

4

Advanced

Allows all constants to be displayed or changed.

D

The control method setting also affects which constants can be displayed and changed. Refer to chapter
NO TAG User Constant Lists.

D

The constants required for basic operation can be displayed and changed in the Basic level, but this
section also describes constants that can be set only in the Advanced level, so set the access level to
Advanced.

Changing the Access Level

The following procedure shows how to change from Quick-Start to Advanced.

Step

Key Sequence

Digital Operator Display

Remarks

1

MENU

MC5

Main Menu

Operation

Displays operation mode.

2

MC5

Main Menu

Initialize

Displays initialize mode.

3

DATA

ENTER

Select Language

English

Puts the Unit in initialize mode.
(Select Language display)

4

Access Level

Quick-Start

Displays the Access Level (A1-01).

5

DATA

ENTER

A1-01

=

2

Quick-Start

Displays the constant setting for
A1-01.

6

Depress Twice.

A1-01

=

4

Advanced

Displays Advanced.

7

DATA

ENTER

Entry Accepted

Writes the new setting.

Access Level

Advanced

Returns to the Access Level display.