Advanced Operation

7.4.3 Setting/Adjusting the Winding Change Constants

- 70

MC Answerback error detection: P1-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

P1-03

MC Answerback error
detection

0.20 to 1.00

sec

0.20

A

A

D

This constant determines the waiting time for the MC (Magnetic Contactor) answerback error detec-
tion. Constant setting is valid when one of the multi-function digital input constants (H1-01 to H1-06)
has been set to 81 or 82.

Motor constant selection: P1-04

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

P1-04

Motor constant selection

0 1

--

1

A

A

D

Select the motor constants allocated for the types of winding to be used.

D

Settings

Setting

Function

0

Motor 1 constants (E1 E2) are used for Y-winding, and motor 2 constants (E3 E4 E5) are
used for -winding

1

Motor 2 constants (E3 E4 E5) are used for Y-winding, and motor 2 constants (E1 E2) are
used for -winding

Programming mode valid/invalid during run: P1-05

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

P1-05

Programming mode val-
id/invalid during run

0 1

--

1

A

A

D

Settings

Setting

Function

0

Disabled

1

Enabled

D

When set to 1, it is possible to select programming mode by pressing MENU or ESC key. Motor coast
to a stop when winding change is performed while in programming mode.

D

If set to 0, stopping during a free run can be prevented, but the program mode cannot be selected while
running.