Advanced Operation

7.3.1 Application Constants: b

- 20

J

Speed Search: b3-01 to b3-03

The speed search function finds the speed of a coasting motor and starts up smoothly from that speed. It
is effective in situations such as switching from a commercial power supply.

Speed Search Selection at Start: b3-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

b3-01

Speed search selection
at start

0 1

--

0 *

A

A

*

When the control method is switched, the factory setting changes as follows:

open-loop vector 0; flux vector: 1

D

Settings

Setting

Contents

0

Speed search disabled:

Motor starts from minimum output frequency.

1

Speed search enabled:

Speed search is performed from maximum output frequency and
motor is started. (In control methods with PG, i.e., V/f with PG feed-
back and flux vector, motor starts from the motor speed.)

D

Set “1” to use the speed search function. A speed search is performed each time the run command is
input.

D

To use speed search freely in control methods without PG, i.e., V/f control and open-loop vector con-
trol, set the multi-function contact input selection (H1-01 to H1-06) to 61 or 62 (external search com-
mand). (See para 7.3.5.)

Speed Search Operating Current, Speed Search Deceleration Time, and Min. Baseblock Time:
b3-02, b3-03, L2-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

b3-02

Speed search operating
current

0

200

%

100

A

b3-03

Speed search decelera-
tion time

0.1

10.0

s

2.0

A

L2-03

Min. baseblock time

0.0

0.5

s

0.5

*

B

B

*

The factory setting varies depending on the Inverter capacity. The values shown in the table

are for 200 V class Inverters of 0.4 kW.

D

For the speed search operating current (b3-02), set the operating current for the speed search. If restart-
ing is not possible with the setting, then lower the setting.

D

Set the speed search operating current as a percentage of the Inverter’s rated output current, with the
Inverter’s rated output current taken as 100%.

D

For the speed search deceleration time (b3-03), set the output frequency deceleration time for while
the speed search is being performed. Set the time required to decelerate from the maximum output fre-
quency to 0 Hz.

D

Speed search deceleration (b3-03) can be used for the Speed search after winding change.

D

When the speed search and DC injection braking are set, set the minimum baseblock time (L2-03). For
the minimum baseblock time, set the time to wait for the motor’s residual voltage to dissipate. If an
overcurrent is detected when starting a speed search or DC injection braking, raise the setting to pre-
vent a fault from occurring.

Run command

OFF

ON

Maximum output
frequency

Deceleration time set for b3-03

Frequency
reference
that is set

Output frequency

Minimum baseblock time (L2-03)

b3-02

Output current

Fig

7.10

Speed Search Timing Chart

7