Yaskawa VS-626 MC5 User Manual

Page 187

Advertising
background image

7.3

Common Functions

- 49

J

Momentary Power Loss Settings: L2-01 to L2-05

Momentary Power Loss Detection: L2-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L2-01

Momentary power loss
detection

0 to 2

--

0

B

B

D

Settings

Setting

Function

0

Disabled. (An undervoltage fault is detected when there is a momentary power loss.)

1

Enabled. (Restarts if power is restored within the L2-02 time. An under-voltage fault is detected
for a longer power loss.)

2

Enabled during CPU operation. (Restarts if power is restored while the CPU is operating. An
undervoltage fault is not detected.)

D

This constant specifies the processing that is performed when a momentary power loss occurs.

D

When power loss ridethru is enabled (setting 1 or 2), operation will be restarted after a speed search
if the power is restored within the allowed time interval.

D

When power loss ridethru is disabled (setting 0), an undervoltage fault will be detected if power is in-
terrupted for more than 15 ms.

Momentary Power Loss Ridethru Time: L2-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L2-02

Momentary power loss
ridethru time

0.0 to 2.0

s

0.7

B

B

D

The factory setting depends on the Inverter capacity. The factory setting shown in the table is for a 200
V class, 0.4 kW Inverter. (See page NO TAG.)

D

This setting is valid only when constant L2-01 is set to 1. Set the power loss ridethru time in seconds.