3.5

Wiring Control Circuit Terminals

- 21

3.5.2 Control Circuit Terminal Functions

The functions of the control circuit terminals are shown in Table 3.9. Use the appropriate terminals for the
correct purposes.

Table

3.9

Control Circuit Terminals

Type

No.

Signal Name

Function

Signal Level

1

Forward run/stop command

Forward run when CLOSED; stopped when OPEN.

2

Reverse run/stop command

Reverse run when CLOSED; stopped when OPEN.

3

External fault input

Fault when CLOSED; normal
when OPEN.

S

4

Fault reset

Reset when CLOSED

Se-

quence

input

5

Multi-step speed reference 1
(Master/auxiliary switch)

Auxiliary frequency reference
when CLOSED.

Multi-function contact in-
puts

Command signals can be

24 VDC, 8 mA
Photocoupler isolation

input

signals

6

Multi-step speed reference 2

Multi-step setting 2 when
CLOSED.

Command signals can be

selected by setting H1-01 to
H1-06.

Photocoupler isolation

7

Jog frequency reference

Jog run when CLOSED.

H1-06.

8

External baseblock

Inverter output stopped when
CLOSED.

11

Sequence input common



15

15 V power output

15 V power supply for analog references

15 V
(Max. current: 20 mA)

33

--15 V power output

--15 V power supply for analog references

--15 V
(Max. current: 20 mA)

Analog

13

Master speed frequence refer-

--10 to 10 V/--100% to 100%

0 to 10 V/100%

--10 to 10 V (20 k ),
0 to 10 V (20 k )

Analog

input

signals

14

Master speed frequence refer-
ence

4 to 20 mA/100%, --10 to +10 V/--100% to 100%
0 to +10 V/100%

4 to 20 mA (250 )

g

16

Multi-function analog input

--10 to 10 V/--100% to 100%
0 to 10 V/100%

Auxiliary analog input
(H3-05)

--10 to 10 V (20 k ),
0 to 10 V (20 k )

17

Control common





12

Shield wire, optional ground
line connection point





9

Running signal (1NO contact)

Operating when CLOSED

Dry contacts
Contact capacity:

10

Running signal (1NO contact)

Operating when CLOSED.

M lti f

ti

t

t

Contact capacity:
1 A max. at 250 VAC
1 A max. at 30 VDC

Se-

quence

25

Zero speed detection

Zero level (b2-01) or below
when CLOSED

Multi-function outputs

Open-collector output

quence

output

signals

26

Speed agree detection

Within

r2 Hz of set frequency

when CLOSED.

Open-collector output
50 mA max. at 48 V*

signals

27

Open-collector output common



18

F

lt

h

CLOSED

18

d 20

Dry contacts
C

t

t

it

19

Fault output signal (SPDT)

Fault when CLOSED across 18 and 20
Fault when OPEN across 19 and 20

y

Contact capacity:
1 A max at 250 VAC

20

p

g

(

)

Fault when OPEN across 19 and 20

1 A max. at 250 VAC
1 A max. at 30 VDC

Analog

21

Frequency output

0 to 10 V/100% frequency

Multi-function analog moni-
tor 1
(H4-01, H4-02)

0 t

10 V

5%

Analog

output

i

l

22

Common



0 to 10 V max. 5%
2 mA max.

output

signals

23

Current monitor

5 V/Inverter’s rated current

Multi-function analog moni-
tor 2
(H4-04,H4-05)

2 mA max.

*

When driving an L load, such as a relay coil, always insert a flywheel diode as shown in Figure 3.18.

External power

:

48 V max.

Flywheel diode

Coil

50 mA max.

The rating of the flywheel diode
must be at least as high as the cir-
cuit voltage.

Fig

3.18

Flywheel Diode Connection

21

22

23

9

10

25

26

27

33

18

19

20

11

12(G)

1

2

3

4

5

6

7

8

13

14

15

16

17

Fig

3.19

Control Circuit Terminal Arrangement