3 operation errors – Yaskawa VS-626 MC5 User Manual

Page 252

Advertising
background image

Troubleshooting

9.1.3 Operation Errors

- 8

9.1.3 Operation Errors

After the constants have been set, an operation error will occur if there is an invalid setting or a contradiction
between two constant settings.

It won’t be possible to start the Inverter until the constants have been set correctly. (The minor fault output
and fault contact output will not operate, either.)

When an operation error has occurred, refer to the following table to identify and correct the cause of the er-
rors.

Table

9.3

Operation Error Displays and Incorrect Settings

Display

Meaning

Incorrect settings

OPE01

kVA Selection

Incorrect Inverter capacity
setting

The Inverter capacity setting doesn’t match the Unit. (Contact your Yaskawa repre-
sentative.)

OPE02

Limit

Constant setting range error

The constant setting is outside of the valid setting range.

OPE03

Terminal

Multi-function input selection
error

One of the following errors has been made in the multi-function input (H1-01 to
H1-06) settings:

S The same setting has been selected for two or more multi-function inputs.
S An up or down command was selected independently. (They must be used together.)
S The up/down commands (10 and 11) and Accel/Decel Ramp Hold (A) were selected

at the same time.

S Speed Search 1 (61, maximum output frequency) and Speed Search 2 (62. set fre-

quency) were selected at the same time.

S External Baseblock NO (8) and External Baseblock NC (9) were selected at the same

time.

S The Terminal 13/14 Switch (1F) was selected, but the terminal 14 function selector

(H3-09) wasn’t set to frequency reference (1F).

OPE05

Sequence Select

Option Card selection error

The Option Card was selected as the frequency reference source by setting b1-01 to
3, but an Option Card isn’t connected.

OPE06

PG Opt Missing

Control method selection er-
ror

Flux vector control was selected by setting A1-02 to 3, but a PG Speed Control Card
isn’t connected.

OPE07

Analog Selection

Multi-function analog input
selection error

S The same setting (other than 1F) has been selected for H3-05 and H3-09.
S An A1-14B Analog Reference Card is being used and F2-01 is set to 0, but a multi-

function input (H1-01 to H1-06) has been set to Option/Inverter Selection (2).

OPE08

Elevator Table

Constant selection error

A setting has been made that is not required in the current control method.

Ex.:

A function used only with flux vector control was selected for open-loop
vector control.

OPE10

V/f Ptrn Setting

V/f data setting error

Constants E1-04, E1-06, E1-07, and E1-09 do not satisfy the following conditions:

S E1-04 (FMAX)

E1-06 (FA)

E1-07 (FB)

E1-09 (FMIN)

OPE11

CarrFrg/On-Delay

Constant setting error

One of the following constant setting errors exists.

S The carrier frequency upper limit (C6-01) > 5 KHz and

the carrier frequency lower limit (C6-02)

5 KHz.

S The carrier frequency gain (C6-03) > 6 and (C6-01) > (C6-02).
S Upper/lower limit error in C6-01 to 03 or C8-15.

OPE12

Winding change sequence
error

One of the following errors exists.

S Multi-function digital input is set to 80 (winding change) and 16 (Motor 2 selection)

at the same time.

S Multi-function digital input is set to 81 and 82 at the same time.
S Multi-function digital input is set to 81, or b1--02 is not set to 5 when P1-01 is not 0.

ERR

EEPROM R/W Err

EEPROM write error

A verification error occurred when writing EEPROM.

S Try turning the power supply off and on again.
S Try setting the constants again.