Advanced Operation

7.3.6 Protective Functions: L

- 54

User

Constant

Number

Valid Access Levels

Factory

Setting

Unit

Setting

Range

Change

during

Opera-

tion

Name

User

Constant

Number

Flux Vector

Open Loop

Vector

Factory

Setting

Unit

Setting

Range

Change

during

Opera-

tion

Name

L4-03

Speed agree detection
level (+/--)

--400.0 to

+400.0

Hz

0.0

A

A

L4-04

Speed agree detection
width (+/--)

0.0 to 20.0

Hz

2.0

A

A

D

Set these constants when outputting one of the frequency agree or frequency detection signals from
a multi-function output. Table 7.10 shows the relationship between these constants and the output sig-
nals.

D

Motor speed is detected at Flux Vector Control.

Table

7.10

Constants and Output Signals

Constant

Related output settings

Constant function

Speed Agree Level
(Absolute value)

Fref/Set Agree 1
Frequency Detection 1 >
Frequency Detection 2 <

Set the frequency (or motor speed) that
you want to detect in Hz.
The set speed is an absolute value, so the
speed is detected in forward or reverse.

Speed Agree Width
(Absolute value)

Fref/Fout Agree 1
Fref/Set Agree 1
Frequency Detection 1 >
Frequency Detection 2 <

Set the frequency (or motor speed) detec-
tion range in Hz.

Speed Agree Level
+/--
(Signed value)

Fref/Set Agree 2
Frequency Detection 3 >
Frequency Detection 4 <

Set the frequency (or motor speed) that
you want to detect in Hz.
Set positive values for forward, negative
values for reverse.

Speed Agree Width
+/--
(Signed value)

Fref/Fout Agree 2
Fref/Set Agree 2
Frequency Detection 3 >
Frequency Detection 4 <

Set the frequency(or motor speed) detec-
tion range in Hz.

D

Set the corresponding setting in the multi-function output (H2-01, H2-02, or H2-03) to output the de-
sired Fref/Fout Agree signal, Fref/Set Agree signal, or Frequency Detection signal.

Function

Setting

Fref/Fout Agree 1

2

Fref/Set Agree 1

3

Frequency Detection 1

4

Frequency Detection 2

5

Fref/Fout Agree 2

13

Fref/Set Agree 2

14

Frequency Detection 3

15

Frequency Detection 4

16

Frequency Detection Operation: L4-05

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L4-05

Operation when fre-
quency reference is
missing

0 1

--

0

A

A

D

The frequency reference is considered lost when the frequency reference voltage drops by 90% for
more than 400 ms.

7