3.6Wiring Check

- 23

3.5.4 Control Circuit Wiring Precautions

D

Separate control circuit wiring (terminals 1 to 33) from main circuit wiring (terminals R, S, T, B1, B2,
U, V, W, ©, ¨1, ¨2, and ¨3) and other high-power lines.

D

Separate wiring for control circuit terminals 9, 10, 18, 19, and 20 (contact outputs) from wiring for
terminals 1 to 8, 21, 22, 23, 25, 26, 27, 33 and 11 to 17.

D

Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults. Process
cable ends as shown in Figure 3.21.

D

Connect the shield wire to terminal 12(G).

D

Insulate the shield with tape to prevent contact with other signal lines and equipment.

Do not connect here.

Connect to shield sheath
terminal at VS-626MC5
(terminal

12

)

Shield sheath

Armor

Insulate with tape

Fig

3.21

Processing the Ends of Twisted-pair Cables

3.6

Wiring Check

Check all wiring after wiring has been completed. Do not perform a buzzer check on control circuits.

D

Is all wiring correct?

D

Have any wire clippings, screws, or other foreign material been left?

D

Are all screws tight?

D

Are any wire ends contacting other terminals?