Yaskawa VS-626 MC5 User Manual

Page 160

Advertising
background image

Advanced Operation

7.3.2 Tuning Constants: C

- 22

J

Motor Slip Compensation: C3-01 to C3-04

D

The motor slip compensation function calculates the motor torque according to the output current, and
sets gain to compensate for output frequency.

x

This function is used to improve speed accuracy when operating with a load.

Slip Compensation Gain: C3-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

C3-01

Slip compensation gain

0.0 to 2.5

Mul-

tiple

1.0 *

B

B

*

When the control method is switched, the factory setting changes as follows:

open-loop vector 0; flux vector: 1.0

x

When “1.0” is set, this function compensates for the rated slip that has been set, by the rated torque
output.

x

With flux vector control, this becomes the gain to compensate for slip caused by motor temperature
variation. (Refer to Slip Compensation Gain: C3-01 under 7.2.2.)

Motor Slip Compensation Gain Adjustment Procedure

1. Correctly set the motor rated slip (constant E2-02) and the motor no-load current (constant E2-03).

x

The motor rated slip can be calculated by means of the following equation, using the numbers that
are shown on the motor nameplate.
Motor rated slip =
Motor rated frequency (Hz) -- rated speed (r/min) x motor (No. of poles) / 120

x

Set the values at the rated voltage and rated frequency for the motor no-load current. With vector
control, the motor rated slip is automatically set by autotuning.

2. Set the slip compensation gain (constant C3-01 to “1.0.” (If it is set to “0.0,” slip compensation will

be disabled.)

3. Operate with a load, measure the speed, and adjust the slip compensation gain (in increments of 0.1).

x

If the speed is lower than the target value, increase the slip compensation gain.

x

If the speed is higher than the target value, decrease the slip compensation gain.

Slip Compensation Primary Delay Time: C3-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

C3-02

Slip compensation pri-
mary delay time

0 to 10000

ms

200

A

D

This constant does not normally need to be set. Adjust the slip compensation primary delay time if the
motor slip compensation responsiveness is low, or if the speeds are unstable.

x

If responsiveness is low, lower the setting.

x

If speeds are unstable, raise the setting.

Slip Compensation Limit: C3-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

C3-03

Slip compensation limit

0 to 250

%

200

A

D

Constant C3-03 sets the slip compensation limit as a percentage of motor rated slip (E2-02), with the
motor rated slip taken as 100%.

D

If the speed is lower than the target value and does not change even when the slip compensation gain
is adjusted, it is possible that the slip compensation limit has been reached. Raise the limit and then
check again. Make sure, however, that the value of the sum of the reference frequency and the slip com-
pensation limit does not exceed the speed capacity of the machinery.

D

The limit is as shown in Figure 7.12 in the constant torque and constant output areas.

7

Advertising