Yaskawa VS-626 MC5 User Manual

Page 149

Advertising
background image

7.2

Flux Vector Control

- 11

7.2.1 Torque Limit Function

With flux vector control, the torque limit can be applied at an arbitrary value because the torque output
by the motor is calculated internally.
The torque limit function is useful when the load cannot sustain a torque above a certain level or regenera-
tive torque above a certain level.

The two ways to apply a torque limit are listed below.

D

Setting torque limits with the constants

D

Limiting torque with the analog inputs

The lower torque limit will be used if both of these methods are set. The accuracy of the torque limit is

r5% at all frequencies.

J

Setting a Torque Limit with Constants: L7-01 to L7-04

D

Torque limits can be set separately for the 4 ways that torque can be applied: forward torque, reverse
torque, forward regenerative torque, and reverse forward regenerative torque.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L7-01

Forward torque limit

0 to 300

%

200

B

B

L7-02

Reverse torque limit

0 to 300

%

200

B

B

L7-03

Forward regenerative
torque limit

0 to 300

%

200

B

B

L7-04

Reverse regenerative
torque limit

0 to 300

%

200

B

B

D

Figure 7.5 shows the relationship between each constant and the output torque.

L7-04

L7-01

L7-02

L7-03

Output torque

Forward
direction

Reverse
direction

Motor speed

Reverse

Forward

Regenerative

torque

Regenerative

torque

Fig

7.5

Torque Limit Function

D

When the torque limit function is used, the torque control has priority and motor speed control and
compensation will be disregarded, so the acceleration/deceleration times might be lengthened and mo-
tor speed might be reduced.

J

Limiting Torque with Analog Inputs: H3-05, H3-09

The following two analog inputs that can be used to limit torque. Use either or both of these inputs as need-
ed with constants H3-05 and H3-09.

D

Multi-function analog input terminal 16

D

Frequency reference (current) terminal 14

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

H3-05

Multi-function analog
input (terminal 16)

0 to 1F

--

0

B

B

H3-09

Multi-function analog
input (terminal 14)

1 to 1F

--

1F

A

A

7

Advertising