6.1

Common Settings

- 15

Three-step Speed Operation Example

The following example shows three-step speed operation with frequencies set at Inverter constants.

D

Sequence

Output frequency

Forward/reverse run
command,
terminal 1 or 2

Multi-step speed reference
1, terminal 5

Multi-step speed reference
2, terminal 6

d1

-

01

d1

-

02

d1

-

03

OPEN

CLOSED

OPEN

CLOSED

OPEN

CLOSED

D

Connections

VS

-

626MC

5

Forward Run/Stop

1

2

6

5

11

IM

U

V

W

R

S

T

R

S

T

Reverse Run/Stop

Multi-step speed
reference 1
Multi-step speed
reference 2

D

User Constant Settings

Constant No.

Name

Setting

A1-01

Constant access level

3: Basic (B)

b1-01

Reference selection

0: Operator

d1-01

Frequency reference 1

Hz frequency setting

d1-02

Frequency reference 2

Hz frequency setting

d1-03

Frequency reference 3

Hz frequency setting

H1-03

Multi-function input (terminal 5)

3: Multi-step speed reference 1 (factory setting)

H1-04

Multi-function input (terminal 6)

4: Multi-step speed reference 2 (factory setting)

H3-05

Multi-function input (terminal 16)

1F: Not used

Terminal 6 would not be needed if 2-step speed operation were required.