7.3

Common Functions

- 21

7.3.2 Tuning Constants: C

J

S-curve Characteristic Function: C2-01 to C2-04

D

Using the S-curve characteristic function for acceleration and deceleration can reduce shock to the ma-
chinery when stopping and starting.

D

With the Inverter, S-curve characteristic times can be set respectively for beginning acceleration, end-
ing acceleration, beginning deceleration, and ending deceleration.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

C2-01

S-curve characteristic
time at acceleration start

0.00 to 2.50

s

0.20

A

A

C2-02

S-curve characteristic
time at acceleration end

0.00 to 2.50

s

0.20

A

A

C2-03

S-curve characteristic
time at deceleration start

0.00 to 2.50

s

0.20

A

A

C2-04

S-curve characteristic
time at deceleration end

0.00 to 2.50

s

0.00

A

A

D

The relation between these constants is shown in Figure 7.11.

Output
frequency

C2-01

C2-02

C2-03

C2-04

Time

Run command

OFF

ON

Fig

7.11

Setting S-curve Characteristics

D

When the S-curve characteristic time is set, the acceleration and deceleration times will be lengthened
as follows:

x

Acceleration time =
Selected acceleration time + (S-curve at beginning of acceleration + S-curve at end of acceleration)
/ 2

x

Deceleration time =
Selected deceleration time + (S-curve at beginning of deceleration + S-curve at end of decelera-
tion) / 2

7