Yaskawa VS-626 MC5 User Manual

Page 216

Advertising
background image

User Constants

8.2.2 Autotuning Constants: C

- 8

J

S-curve Acceleration/Deceleration: C2

Consta

nt

Name

Set-

Facto-

Change

during

Control Methods

nt

Num-

ber

Display

Description

Set

ting

Range

Facto

ry Set-

ting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

C2-01

S-curve charac-
teristic time at ac-
celeration start

All sections of the S-curve characteristic
time are set in seconds units

0.0 to

2.50

0.20

A

A

- 21

SCrv Acc @ Start

time are set in seconds units.

When the S-curve characteristic time is

2.50

C2-02

S-curve charac-
teristic time at ac-
celeration end

When the S-curve characteristic time is

set, the accel/decel times will increase
by only half of the S-curve characteris-
tic times at start and end.

0.0 to

2.50

0.20

A

A

- 21

SCrv Acc @ End

Run com-

ON

OFF

2.50

C2-03

S-curve charac-
teristic time at de-
celeration start

Output frequency

C1-02

C1-03

Run com-
mand

ON

OFF

0.00 to

2 50

0.20

A

A

- 21

C2 03

SCrv Dec @
Start

C1-01

C1 03

C1-04

2.50

0.20

A

A

- 21

C2-04

S-curve charac-
teristic time at de-
celeration end

C1-01

C1-04

Time

0.00 to

2.50

0.00

A

A

- 21

SCrv Dec @ End

2.50

J

Motor Slip Compensation: C3

Constant

Name

Setting

Factory

Change

during

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

C3-01

Slip compensation
gain

Used to improve speed accuracy
when operating with a load.

Usually setting is not necessary.

When actual speed is low, in-
crease the set value.
When actual speed is high, de-

0.0 to

2 5

1.0 *

B

B

- 15

22

C3 01

Slip Comp Gain

When actual speed is high, de-
crease the set value.
In flux vector control mode this
function becomes gain to com-
pensate for slip caused by tem-
perature variation.

2.5

1.0

B

B

- 22

C3-02

Slip compensation
primary delay time

Slip compensation primary delay
time is set in ms units.

Usually setting is not necessary.

Adjust when slip compensation
responsiveness is low, or speed is
not stabilized.

0 to

10000

200 *

A

- 22

C3 02

Slip Comp Time

not stabilized.

When responsiveness is low, de-
crease the set value.
When speed is not stabilized, in-
crease the set value.

10000

200

A

- 22

C3-03

Slip compensation
limit

Sets the slip compensation limit as
a percentage of motor rated slip

0 to 250

200

A

- 22

C3 03

Slip Comp Limit

a percentage of motor rated slip.

0 to 250

200

A

- 22

C3-04

Slip compensation
selection during re-
generation

0: Disabled.
1: Enabled.

When the slip compensation dur-

ing regeneration function has
been activated, as regeneration
capacity increases momentarily,

0 1

0

A

- 23

Slip Comp Regen

capacity increases momentarily,
it may be necessary to use a
braking option (braking resistor,
Braking Resistor Unit or Braking
Unit.)

C3-05

Flux calculation meth-
od

Used to set the flux calculation
method.
0: Flux is calculated based on the

output frequency after com-
pensation

0 1

0

A

----

C3 05

Flux Select

pensation.

1: Flux is calculated based on the

output frequency before com-
pensation.

0 1

0

A

----

8