Yaskawa VS-626 MC5 User Manual

Page 197

Advertising
background image

7.3

Common Functions

- 59

Carrier Frequency Reduction Selection: L8--17 (fot SPEC: F)

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L8-17

Carrier frequency reduc-
tion selection 2

0 to 3

--

1

A

D

Settings

Setting

Function

0

No carrier frequency reduction.

1

With carrier frequency reduction.

2

For factory adjustments.

3

For factory adjustments.

D

If metallic noise (carrier noise) from the motor is a problem when carrier frequency is reduced (less
than 6 Hz), set L8--17 to 0 (no carrier frequency reduction), and L8--19 (OL2 characteristics selection
at low speeds) to 1 (enabled).

D

Do not L8--17 and L8--19 to 0 at the same time when using V/f control open loop vector control.

OL2 characteristics Selection at Low Speeds: L8--19 (for SPEC: F)

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L8-19

OL2 characteristics
selection at low speeds

0 1

--

0

A

A

D

Settings

Setting

Function

0

OL2 characteristics at low speeds disabled.

1

OL2 characteristics at low speeds enabled.

D

When using OL2 to trip at low speeds (less than 6 Hz) despite a light load, set L8--17 to 1 (with carrier
frequency reduction) and L8--19 (OL2 characteristics selection at low speeds) to 0 (disabled).
However, do not set 18--19 to 0 for 400 V class, 185 to 300 kW Inverters.

D

Do not L8--17 and L8--19 to 0 at the same time when using V/f control open loop vector control.

D

Reduce the carrier frequency (C6--01) to 2 kHz when continuously operating at low speeds with heavy
loads when using flux vector control.