Advanced Operation

7.3.5 External Terminal Functions: H

- 38

D

For the operation selection, select the processing method that you want to be performed when a fault
has been detected.

x

Deceleration to stop: A fault is output and the output stopped in the selected deceleration time.

x

Coast to stop: A fault is output and the Inverter output is cut off.

x

Emergency stop: A fault is output and the output stopped in the emergency stop time (C1-09).

x

Continue operation: An alarm is output and operation continues.

D

When an alarm is going to be output externally, be sure to set one of the multi-function outputs (H2-01,
02, and 03) to alarm (setting 10).

D

An external fault setting cannot be set in more than one multi-function input.

D

Unlike other constant settings, the external fault settings have an input procedure, as shown in the fol-
lowing diagrams.

Setting Procedure

1. When setting an external fault function, press the Enter Key when “External Fault” is displayed to

bring up the “Input Level” display.

External Fault

Input level

Detection

method

Operation

Selection

DATA

ENTER

ESC

Fig

7.22

Setting Procedure for External Fault Function

2. Press the Increment Key to switch displays as follows:

“Detection Method”

o “Operation Selection” o “Input Method”