LV - Low Voltage threshold

Compatibility: All drives
Affects:

Under voltage alarm and fault

Sets or requests the low voltage threshold for under voltage alarm / fault conditions. In AC drives (e.g. BLuAC5
and STAC6) an under voltage condition causes a Drive Fault, which disables the motor outputs of the drive. In DC
drives (SV, ST, and STM) an under voltage condition causes an Alarm. If desired, the user can change the low
voltage threshold of the drive, however in most applications it is neither necessary nor recommended. The factory
default for low voltage threshold is set to both protect the drive from damage and work with the widest range of
supply voltages possible.

Command Details:

Structure

LV{Parameter #1}

Type

BUFFERED

Usage

READ/WRITE

Non-Volatile

Yes

Register Access

None

Parameter Details:

Parameter #1

Low voltage threshold

- units

All drives except BLuAC5: 0.1 volts DC
BLuAC5: 1 volt DC

- range

BLuDC: 18 to 40
BLuAC: 90 to 300
STAC6: 90 to 160
ST5: 12 to 75
ST10: 12 to 75
SV7: 12 to 75
STM: 10 to 75

Examples:

Command

Drive sends

Notes

LV

LV=180

Low voltage threshold of ST5 set at 18 VDC

LV200

-

Set low voltage threshold of ST5 drive to 20 VDC

LV

LV=900

Low voltage threshold of STAC6 set at 90 VDC (bus voltage)

LV

LV=90

Low voltage threshold of BLuAC5 set at 90 VDC (bus voltage)