Qc - queue call, Command details, Parameter details – Applied Motion RS-232 User Manual

Page 163: Examples

Advertising
background image

163

920-0002 Rev. I

2/2013

Host Command Reference

QC - Queue Call

Compatibility: Q drives only
See also:

QX, QE, QL commands

Loads a program segment from non-volatile memory into the queue and begins executing at line #1. Loads the
“calling” segment location and the line where the call occurred into a call “stack”. When a QC command without
a parameter is encountered in the segment a “return” to the calling segment is activated. The “calling” segment is
loaded from non-volatile memory back into the queue and begins executing at the line immediately following the
line number of the original “calling” QC command.

The call stack can go 5 calls deep which means you can nest up to 5 calls. If the number of calls before a “return”
(QC with no parameter) is encountered exceeds 5 the “calling” QC command (with parameter) is ignored. If a
“return” is encountered without a previous call, the return is ignored.

Command Details:

Structure

QC{Parameter #1}

Type

BUFFERED

Usage

WRITE ONLY

Non-Volatile

NO

Register Access

None

Parameter Details:

Parameter #1

Program segment, no parameter means return to calling
segment

- units

integer

- range

1 - 12 = segment 1 - 12
no parameter = return to calling segment

Examples:

Command

Drive sends

Notes

QC4

-

Call segment 4

QC

-

Return to calling segment