Host Command Reference

BR - Baud Rate

Compatibility: All drives
Affects:

Serial communications

See also:

TD, PB, PM, PR commands

Sets or requests the bit rate (baud) for serial communications. At power up a drive will send its power-up packet
at 9600 baud. If a response from a host system (such as a software application from Applied Motion) is not
detected after 1 second and the drive is configured for SCL or Q operation (see PM command) the drive will set
the baud rate according to the value stored in the Baud Rate NV parameter. A Host system can set the baud rate
at anytime using this command. See Appendix B, “Host Serial Communications” for details.

NOTE 1: Setting the value takes effect immediately.

NOTE 2: Due to processor speed limitations, -Si drives can accept only parameter values 1, 2 or 3. -S and -Q
drives will accept parameter values of 1-5.

Command Details:

Structure

BR{Parameter #1}

Type

BUFFERED

Usage

READ/WRITE

Non-Volatile

YES

Register Access

None

Parameter Details:

Parameter #1

Baud rate (see above)

- units

integer code

- range

1 = 9600 bps
2 = 19200
3 = 38400
4 = 57600 (-S and -Q drives only)
5 = 115200 (-S and -Q drives only)

Examples:

Command

Drive sends

Notes

BR2

-

Baud rate is immediately set to 19200