Pb - power-up baud rate, Command details, Parameter details – Applied Motion RS-232 User Manual

Page 151: Examples

Advertising
background image

151

920-0002 Rev. I

2/2013

Host Command Reference

PB - Power-up Baud Rate

Compatibility: All drives
See also:

BR, PR, TD commands

Sets or requests the power-up baud rate for serial communications. When executed, this command sets the baud
rate and immediately saves it to non-volatile memory. At power-up the drive defaults to 9600 baud. If an Applied
Motion software application is not detected after 1 second and the drive is configured for host operation the drive
will set the baud rate according to the value stored in the Power-up Baud Rate non-volatile parameter. A host
system can change the baud rate at any time.

NOTE: Setting the baud rate takes effect immediately.

Command Details:

Structure

PB{Parameter #1}

Type

BUFFERED

Usage

READ/WRITE

Non-Volatile

Yes (see note below)

Register Access

None

Parameter Details:

Parameter #1

Baud rate code

- units

integer code

- range

1 = 9600
2 = 19200
3 = 38400
4 = 57600
5 = 115200

NOTE: This data is saved to non-volatile memory immediately upon execution. It is not required to execute the
SA command to save to non-volatile memory.

Examples:

Command

Drive sends

Notes

PB2

-

Power-up baud rate is set to 19200 and this value is immediately

saved to non-volatile memory

PB PB=2