Ca - change acceleration current, Command details, Parameter details – Applied Motion RS-232 User Manual

Page 44: Example

Advertising
background image

44

920-0002 Rev. I
2/2013

Host Command Reference

CA - Change Acceleration Current

Compatibility: STM Integrated Step Motors
Affects:

Motor accel/decel current and torque

See also:

PA, CC, PC commands

Sets or requests the accel/decel current setting (“peak of sine”) of the stepper drive, also known as the peak
current. CA will only accept parameter values equal to or larger than the current CC setting.

NOTE: CA has no effect in Command Mode 7 (CM7 - Step and Direction mode).

Command Details:

Structure

CA{Parameter #1}

Type

BUFFERED

Usage

READ/WRITE

Non-Volatile

YES

Register Access

“M” (029)
Note: The CA command uses different units than the “M”
register; see Data Registers section for details

Parameter Details:

Parameter #1

Accel/Decel Current

- units

amps (resolution is 0.01 amps)

- range

STM23: 0 - 5.0
STM17: 0 - 2.0

Configurator software may also be used to set all current levels.

Example:

STM17, STM23

Command

Drive Sends

Notes

CA1.75

-

Set accel/decel current to 1.75 amps (peak of sine)

CA CA=1.75