Type 1 message examples – Applied Motion RS-232 User Manual

Page 287

Advertising
background image

287

920-0002 Rev. I

2/2013

Host Command Reference

B7

Unused = 0

Type 1 Message Examples

Example 1: SCL commands required for Point to Point move

AC100

set acceleration rate to 100 rev/sec/sec (6000 rpm/sec)

opcode

0x001E

from

Table

1

operand 0x258 units are 10 rpm/sec, so 6000 rpm/sec is represented by 600 decimal = 258 hex

Type 1 Command Message Payload

Type 1 Response Message Payload

byte 0

0

reserved

byte 0

0

reserved

byte 1

1

message type

byte 1

1

message type

byte 2

0

unused

byte 2

0

unused

byte 3

1E

opcode

byte 3

1E

opcode

byte 4

0

unused

byte 4

?

Status Code MSB

byte 5

0

unused

byte 5

?

Status Code LSB

byte 6

2

operand MSB

byte 6

0

not used

byte 7

58

operand LSB

byte 7

0

not used

DE100

set deceleration rate to 100 rev/sec/sec (6000 rpm/sec)

opcode

0x001F from Table 1

operand 0x258 units are 10 rpm/sec, so 6000/sec is represented by 600 decimal = 258 hex

Type 1 Command Message Payload

Type 1 Response Message Payload

byte 0

0

reserved

byte 0

0

reserved

byte 1

1

message type

byte 1

1

message type

byte 2

0

unused

byte 2

0

unused

byte 3

1F

opcode

byte 3

1F

opcode

byte 4

0

unused

byte 4

?

Status Code MSB

byte 5

0

unused

byte 5

?

Status Code LSB

byte 6

2

operand MSB

byte 6

0

not used

byte 7

58

operand LSB

byte 7

0

not used

VE5

set velocity to 5 rev/sec (300 rpm)

opcode

0x001D from Table 1

operand 0x4B0 units are 0.25 rpm, so 300 rpm is represented by 1200 decimal = 4B0 hex