<5. EtherLCD>

5-25

IM 11B08A01-01E

5.3.4 Remote

A/O

Operation

Navigating to the Remote A/O Operation screen sets the mode to Remote A/O Manual and the
outputs of all 36 remote A/O channels become 4 mA. On the Remote A/O Operation screen,
a command to set values between 0 and 1 is available for each of the up to 36 remote A/O
channels. Navigating to other screens cancels the Remote A/O Manual mode, and according to
the settings, outputs are made from each remote A/O channel.
To set the output value of a remote AO, select the remote A/O number with the cursor, enter the
set value and press the Set/Ent key. Note that this operation must be done in Manual status and
in Stop mode.

1 1 / 1 1 / 2 2
1 5 : 1 5 : 4 5

Remote A/O Operation

(1/N)

R-AO# Set value
> - 1 A
- 2 A
- 3 A
- 4 A
- 5 A
- 6 A
- 7 A
- 8 A
- 9 A

Menu

F1

F2

F3

F4

F5

F6

Figure 5.29

Example of the remote A/O operation screen

F1 (Menu):

Displays the Operation Menu screen.

TIP

For this operation, the user level C or higher is required.

• If the Analog output num is 0 on the GCCU Setup screen, this screen will not be displayed.

Display Item

Name

Set Lower Limit Upper Limit

Unit

Remarks

R-AO #

Remote A/O channel

number

1

36

Number Remote A/O channel number

Set value

–0.2500

1.2500

After the value is set, 0 to 1 is

output as 4 to 20 mA.

* Internally, the value is written

in the MODBUS remote A/O

data table.

* The initial value is 0.0000.

5.3.5

Remote D/O Operation

Navigating to the remote D/O Operation screen sets the mode to Remote D/O Manual and all the
remote D/O contacts are turned Off. On the Remote D/O Operation screen, both the On and Off
commands are available. Navigating to other screens cancels the Remote D/O Manual mode,
and according to the settings, all remote D/O contacts are turned On or Off.
To change the remote D/O status to On or Off, select the remote D/O number with the cursor and
press the Set/Ent key. Note that this operation must be done in Manual status and in Stop mode.