Yokogawa GC8000 Process Gas Chromatograph User Manual

Page 69

Advertising
background image

<1. Overview>

1-42

IM 11B08A01-01E

● In the case where a stream sequence change command is received during the run mode in

the stream sequence status [1A2]

The measurement status is changed to the requested stream sequence status when the

measurement of the currently-measured stream is completed.

In this case, the operation mode remains unchanged from the run mode.

* Requests for changes to the same stream sequence number are invalid.

● In the case where a stream sequence change command is received during the pause mode

in the stream sequence status [1A6]

The measurement status is immediately changed to the requested stream sequence status.
In this case, the operation mode changes to the stop mode and valves are all closed (turned

off).

* Requests for changes to the same stream sequence number are invalid.

Stop

Run

W4

W5

W1

W2

W3

S2

S1

S5

S4

[1A1]

[1A2]

Time

Stream sequence 1

Stream sequence 2

Stream sequence 1

Assinning stream

sequence 2

Assinning stream sequence 1

Run command

Stop

Pause

Run

W4

W5

W1

W2

W3

S2

S1

S5

S4

[1A6]

[1A2]

Time

Stream sequence 1

Stream sequence 2

Stream sequence 1

Assinning stream

sequence 2

Assinning stream sequence 1

Run command

● In the case where a stream specifi cation change command (for continuous measurement)

is received during the run mode in the stream sequence status [1B2]

The measurement status is changed to the requested stream specifi cation status (for

continuous measurement) when the measurement of the currently-measured stream is
completed.

In this case, the operation mode remains unchanged from the run mode.

Run

W4

W1

W2

S2

S1

S4

W4

S4

W4

S4

W4

S4

W4

[1B2]

Time

Stream sequence 1

Stream specification 4 (Continuous)

Assinning stream specification 4 (Continous)

● In the case where a stream specifi cation change command (for N times of measurement) is

received during the run mode in the stream sequence status [1C2]

The measurement status is changed to the requested stream specifi cation status (for

N times of measurement) when the measurement of the currently-measured stream is
completed.

In this case, the operation mode changes from the run mode to the stop mode when the Nth

round of the specifi ed measurement is completed.

2nd Edition : May 11, 2012-00

Advertising