<1. Overview>

1-44

IM 11B08A01-01E

● In the case where a stop command is received during the pause mode in the stream

sequence status [1E6]

The operation mode is immediately changed to the stop mode in the stream sequence

status.

Run

[1E6]

Time

Stream sequence 1

Stop command

W1

W2

S1

* Pause status

Stop

Pause time

● In the case where a forced stop command is received during the run mode in the stream

sequence status [1F2]

The operation mode is immediately changed to the stop mode in the stream sequence

status.

Run

W1

W2

S2

S1

[1F2]

Time

Stream sequence 1

Forced stop command

Stop

● In the case where a forced stop command is received while the operation mode is

scheduled to be changed to the stop mode or pause mode in the stream sequence status
[1F3], [1F4]

The operation mode is immediately changed to the stop mode in the stream sequence

status.

Run

(Waiting for stop or pause)

W1

W2

S2

S1

[1F3] [1F4]

Time

Stream sequence 1

Forced stop command

Stop

2nd Edition : May 11, 2012-00