Yokogawa GC8000 Process Gas Chromatograph User Manual

Page 98

Advertising
background image

<1. Overview>

1-71

IM 11B08A01-01E

When all the calibration (or validation) patterns of which automatic execution is enabled are

completed, the operation mode changes to the stop mode in the stream specifi cation status.

Run

W7

W7

W8

S8

S7

S7

Time

Stream specification 1

Calibration 1

Stream specification 1

Start of automatic calibration

Pause

Stop

● In the case where a stop command is received during the run mode in the (automatic)

calibration/validation status [4E2]

The operation mode is immediately prepared to be changed from the run mode to the stop

mode in the calibration (or validation) status.

The operation mode changes to the stop mode in the previous measurement status when

the current measurement is completed.

Run

W7

W7

W8

S7

S7

Time

Stream sequence 1

Calibration 1

Stream sequence 1

Start of automatic calibration

Stop

Stop

[4E2]

Stop command

● In the case where a forced stop command is received during the run mode in the (manual)

calibration/validation status [4F2]

The operation mode is immediately changed to the stop mode in the previous measurement

status.

● In the case where a forced stop command is received when the operation mode is prepared

to be changed from the run mode to the stop mode in the (manual) calibration/validation
status [4F3]

The operation mode is immediately changed to the stop mode in the previous measurement

status.

Stop

Stop

Run

(Waiting for stop)

W7

W7

S7

S7

Time

Stream sequence 1

Calibration 1

Stream sequence 1

Forced stop command

Start of automatic calibration

[4F2] [4F3]

(Stop command)

[4F3]

2nd Edition : May 11, 2012-00

1