<Appendix D Action of External Input and Output Signals>

App.D-13

IM 11B08A01-01E

Table 11

In the status of stream

sequence 1 or stream

specifi cation 1

Stop to Pause

Turned On when the mode changes to the pause

mode

Stop to Run

Turned On when the mode changes to the run

mode

Run to Pause

Kept turned On

Run to Stop

Turned Off when the mode changes to the stop

mode

Run mode of stream sequence 1* to Run mode of

stream sequence 2

Turned Off when analysis starts for the stream 2

Pause mode of stream sequence 1* to Stop mode

of stream sequence 2

Turned Off when the mode changes to the stop

mode of stream 2

Stop mode of stream sequence 1* to Stop mode of

stream sequence 2
Run mode of stream sequence 2 to Run mode of

stream sequence 1*

Turned On when analysis starts for the stream 1

Pause mode of stream sequence 2 to Stop mode

of stream sequence 1*

Kept turned Off

Stop mode of stream sequence 2 to Stop mode in

the status of stream sequence 1*
Run mode of stream sequence 1 to Run mode of

stream specifi cation 1

Kept turned On

Pause mode of stream sequence 1 to Stop mode

of stream specifi cation 1

Turned Off when the mode changes to the stop

mode of stream 1

Stop mode of stream sequence 1 to Stop mode of

stream specifi cation 1

Kept turned Off

Run mode of stream sequence 1* to Calibration/

Validation

Turned Off when analysis starts for the calibration/

validation stream

Pause mode of stream sequence 1* to Calibration/

Validation

Turned Off when analysis starts for the calibration/

validation stream

Stop mode of stream sequence 1* to Calibration/

Validation

Kept turned Off

*

Same for the case of stream specifi cation 1

1 1 / 1 1 / 2 2
1 5 : 1 5 : 4 5

D/O Setup

Slot # 1 DO # 1
>

- Process assign Stream

- Stream 1 (GCM 1)

Menu

Status

Slot#

DO#

F1

F2

F3

F4

F5

F6

Figure 16 Process Specifi cation: Stream (D/O Setting Screen on GC-HMI EtherLCD)

Operation Mode

The Operation Mode function of D/O is a function to send out information that the operation mode

of each GCM is in the specifi ed mode. The contact output is turned On in the operation mode set

on the D/O setting screen.

One among the following four types of operation mode is set for each contact point.

• Run
• Run (Warming up time)
• Stop
• Pause

2nd Edition : May 11, 2012-00

App.D