RISCO Group LightSYS 2 User Manual

Page 101

Advertising
background image

Installer Programming

Page 101

Quick Keys

Parameter

Default

Range



ZZ

 

Fire 

 

 

For smoke or other types of fire detectors. This option can also be used 
for manually triggered panic buttons or pull stations (if permitted), as 
follows: 

 If violated, it causes an immediate fire alarm, and the Fire/   LED is 

lit (steady). 

 A fault in the wiring (wire open) to any fire zone causes a Fire 

Trouble signal (a rapid flashing of the keypadsʹ FIRE /

 LED). A 

short in the wires will cause an immediate alarm. 



ZZ

 

Panic 

 

 

Used for external panic buttons and wireless panic transmitters. 
If violated, an immediate panic alarm is sounded (if the zone sound is 
not defined as silent or audible panic system control is enabled), 
regardless of the system’s state and panic report is sent to the 
monitoring station. An alarm display will not appear on the keypads. 
If violated, an immediate panic alarm is sounded, regardless of the 
systemʹs state. 



ZZ

 

Special 

 

 

For external auxiliary emergency alert buttons and wireless auxiliary 
emergency transmitters. 
If violated, an immediate auxiliary emergency alarm is sounded, 
regardless of the system’s state and a report is sent to the monitoring 
station. 



ZZ

 

Pulsed Key Switch 

 

Used to arm/Disarm the system. 
Connects an external momentary action keyswitch to any zone terminals 
given this designation. 



ZZ

 

Final Exit

 

 

Zones of this type must be the last detector to be activated on exit or the 
first detector to be activated on entry. When arming the system, the 
related partition arms 10 seconds after this zone is closed, or opened and 
then closed. After it is triggered once, the zone acts as an exit 
(open)/entry 1 zone. 