Installer Programming

Page 77

Quick Keys

Parameter

Default

Range

 

 

Arm Pre‐Warning  

 No

  

Yes/No

 

Related to auto arm/disarm operation. 
YES
: For any partition(s) set up for auto arming, an audible exit delay 
(warning) countdown will commence 4.25 minutes prior to the 
automatic arming. During this period, exit delay beeps will be heard. 
You can enter a valid user code at any time during the countdown to 
delay the partition’s automatic arming by 45 minutes. 
When an “Auto‐Arm” partition is disarmed, as described above, it can 
no longer be automatically armed during the current day. 
The extended 4.25 minutes warning does not apply to automatic partial 
arming. 
NO
: Auto arming for any programmed partition(s) takes place at the 
designated time. The programmed exit delay period and any audible 
signal occur as expected. 



 

Advanced 

 Yes 

Yes/No 

This section refers to the advanced controls in the system. 

 

 

Double Verification  
of Fire Alarms 

 No

  

Yes/No

 

YES: Implemented on detection of smoke or fire for verification. Power 
to the smoke detector(s) in the affected zone is cut off and restored after 
the time defined in the Switch Aux Break delay (page 71). If a 
subsequent detection occurs in the same zone within one minute of the 
first detection, the system emits a fire alarm. 
NO
: No fire alarm verification takes place. 