RISCO Group LightSYS 2 User Manual

Page 122

Advertising
background image

Installer Programming

Page 122

If a zone in the Soak Test list has an alarm during the 14‐day period, the 
keypad indicates to the user that the test has failed. After the user looks at 
the View Trouble option (described in the LightSYS2 User’s Manual), the 
trouble message will be erased. This will be indicated in the event log, but 
no alarm will be generated. The alarmed zone’s 14‐day Soak Test period 
is then reset and restarted.. 

To set up a Soak‐Test. [LightSYS] 

1. From the Install menu, press quick keys 



. The 

following display appears: 

ZONES FOR TEST:
01) ZONE 01 N

2. To put a zone on Soak Test, press 

. The following display 

appears: 
LOCATION 01:
ZONE: 00-32

3.

Press the keys as per the zone number (e.g. 01 for zone 1)

4.  Press 

 to confirm and display the initial menu. 

5. To add a second zone for Soak Test, press and repeat the 

procedure above, ‐OR Press the 

  key to return to the 

previous menu. 



Cross Zones

Default: No cross zoning 

The Zone Crossing menu is used for additional protection from false alarms and contains 
parameters that enable you to link together two related zones. Both must be violated within a 
designated time period (between 1 and 9 minutes) before an alarm occurs. 

This type of linking is used with motion detectors in hostile or false‐alarm prone environments.  

The LightSYS2 allows 10 unique sets of zone links (pairs of zones), which can be manually 
specified, as required. Zones crossed with themselves are valid pairs. They need to register a 
violation twice to trigger the alarm. This process is known as Double Knock. You may want to 
establish a number of zone links, but leave them deactivated at this time (see below). 