RISCO Group LightSYS 2 User Manual

Page 67

Advertising
background image

Installer Programming

Page 67

Step 2: Adding Bus Detector

Refer to section Step 1: Adding Bus Detector to the Main Unit  to assign a bus detector 
to the system. 

Note

When the bus zone is connected to a bus expander, you should define the X in the (x:yy) 
display as the bus expander ID (1,2,3 or 4). The yy represents the bus detector ID 
number (up to 32) as set by the detectorʹs DIP switches. 

Step 3: Set Bus Zone Basic Attributes

1. From the main Installer menu select [1] Zones > [1] Parameters > [1] One by

One

 

2. Select the zone number that the bus zone was assigned to and press 

.  

3. Configure the parameters for the relevant bus detector.  

Note:

In the zone designation XY:ZZ the X represent the Bus Expander ID as set by its dip 
switches.  

Step 4: Programming the Bus Detectors Advanced Parameters

1. From the main Installer menu select [2] Zones > [1] Parameters > [2] By

Category > [7] Advanced > [4] BZ Parameters

2. Select the zone number that the bus zone was assigned to and press 

.  

3. Configure the parameters for the relevant bus detector. 

Exiting Programming Mode

1. Set SW1 – 2 (Default) to OFF position. 
2. Close the main box in order to prevent Front Tamper Alarm. 

3. Press 

 repeatedly to return to ‘Main Menu’. 

4. Press 

>

 to Exit and SAVE your settings. 

Note:

The system will not allow exit from the Installer mode if a ‘Tamper’ or ‘System 
Troubel’ condition exists. Correct any tamper and/or system fault conditions before 
attempting to exit the Installer mode. 

Advertising