Installer Programming

Page 78

System: Controls: Advanced

Quick Keys

Parameter

Default

Range

 

 

Alarm ZE Cut 

 No

  

Yes/No

 

YES: Produces an alarm if the communication between the main panel 
and any expander is lost. A report is transmitted to the MS. 
NO
: No alarm occurs. The system, however, produces a local trouble 
indication. 

 

Code Grand Master 

 No 

 

Yes/No

 

YES: Only a user with the grand master authority level can change all 
user codes, along with the time and date. 
NO
: Users with the grand master and master authority levels can change 
their own user codes, all codes with a lower authority level, and the time 
and date. 

 

Area 

 No

  

Yes/No

 

Changes the system operation to area instead of partition, which then 
changes only the operation of a common zone. 
YES
: When selected, the following points are relevant: 

A common zone will be armed after any partition is armed. 
A common zone will be disarmed only when all partitions are 

disarmed. 

NO: When selected, the following points are relevant: 

A common zone will be armed only when all partitions are armed. 
A common zone will be disarmed when any partition is disarmed.  

 

Global Follower 

 Yes

  

Yes/No

 

YES: Specifies that all zones (that are programmed to follow an 
Exit/Entry delay time) will follow the Exit/Entry delay time of any armed 
partition. 
NO
: Specifies that all zones (that are programmed to follow an entry 
delay time) will follow the entry delay time of only the partitions to 
which they are assigned. 

 

Summer/Winter 

 No

  

Yes/No

 

YES: The LightSYS2 automatically sets its Time of Day clock one hour 
ahead in the spring (on the last Sunday in March) and one hour back in 
the Autumn (on the last Sunday in October). 
NO: No automatic time accommodation is made. 