Using the Installer Non‐Programming Menus

Page 210

Siren Test 

Activates the alarm sound from each BUS sounder, from the Bell terminals on the main 

board and activates utility outputs defined as Bell Trigger 

( ).

   

Strobe Test 

Activates all strobes in connected BUS sounders and activates utility output defined as 

Follow Strobe 

( ).

   

Zone Resistance 

Tests the resistance and voltage level of the wired zones in the system. Use the 

 key to 

toggle between resistance and voltage of each detector 

Diagnostics 

Activates the relevant tests for:  

Main UnitTests the standby battery level of the main board and the system 

version

Bus ZonesPerforms a diagnostic test to the Bus zones in the system and displays 

the relevant information for each detector. 

Zone Expander Performs a diagnostic communication test on installed zone 

expanders and tests its version. 

Power supply: Performs a diagnostic communication test on installed power 

supplied expanders and displays the relevant information for each 
power supply. 

Siren: Performs a diagnostic communication test on installed bus sirens and 

displays the information regarding each siren (depending on the siren 
type)

GSM: Performs a diagnostic test for the following parameters of the plug in GSM 

module:  

 Signal (RSSI): Displays the signal level measured by the GSM module. 

(0=No signal, 5= Very high signal) 

 Version: Displays information regarding the GSM module version 
 IMEI: View the IMEI number of the GSM module. This number is used 

for identification of the LightSYS2 at the RISCO IP receiver when using 
GSM or GPRS communication. 

IP:  Performs a diagnostic test for the following parameters of the plug in IP  

module: 

 IP Address: View the IP address of the LightSYS 
 Version: View the IP module software version 