RISCO Group LightSYS 2 User Manual

Page 162

Advertising
background image

Installer Programming

Page 162

Quick Keys

Parameter

Default

Range



Confirmation 

 

 

The confirmation times relate to the Zone Sequential Confirmation 

(Alarm Confirmation, see 

)

 



Confirm Start (Confirm 
delay time)    

000 

1–120 minutes 

Specifies that the system cannot start a sequential confirmation process 
until the timer has expired. This time starts when the system has set and 
will prevent confirmed alarms being generated in situations when a 
person has been accidentally locked in the building. 



Confirm Time Window    

030 

30–60 minutes 

Specifies a time period that starts when an alarm is triggered for the first 
time. If a second alarm is triggered before the end of the confirmation 
time window, the system will send a confirmed alarm to the monitoring 
station 



Report Split 

 

 

The Report Split menu contains parameters that enable the routing of 
specified events to up to three MS receivers.  



MS Arm/Disarm 

1

st

 backup 2

nd

   

Reports Arming/Disarming (meaning Closings/Openings) events to the 
MS 

 Do not call (no report). 

Send 1

st

: Reports Openings and Closings to MS 1. 

Send 2

nd

: Reports Openings and Closings to MS 2. 

Send 3

rd

: Reports Openings and Closings to MS 3. 

Send all: Reports Openings and Closings to the all defined MS. 

1

st

 Backup 2

nd

: Reports Openings and Closings to MS 1. If 

communication is not established, calls MS 2. 

 1

st

 Backup 2

nd

3rd: Reports to MS 1. If communication is not 

established calls MS 2. If communication is not established again calls the 
MS. 