RISCO Group LightSYS 2 User Manual

Page 221

Advertising
background image

Wiring

Page 221

Wire Gauge

Max Combined Length of ALL Expansion
Bus Wiring

24 AWG 

7/02mm  

150 meters 

492 feet 

22 AWG 

16/02mm 

200 meters 

656 feet 

20 AWG 

24/02mm 

333 meters 

1092 feet 

19 AWG 

28/02mm 

400 meters 

1312 feet 

Table A-3: Wire Gauge

Notes:

For maximum system stability, it is best NOT to exceed a total of 300 meters (1000 
feet) of wire when wiring the Expansion bus. 
For a distance of more than 300 meters, refer to RISCO Group technical support 
service for detailed information. 

 

Total
Auxiliar
y Power
(Max
Current
Draw
per
Branch)

Desired Wire Gauge in Particular Branch

32/02

mm

18 AWG

28/02

mm

19 AWG

24/02 mm

20 AWG

16/02

mm

22 AWG

7/02 mm

24 AWG

Max
Run

Max Run

Max Run

Max Run

Max Run

Meters

Feet

Meters

Feet

Meters

Feet

Meters

Feet

Meters

Feet

20mA 

1195 

3920 

945 

3100 

750 

2460 

472 

1550 

296 

970 

30mA 

793 

2600 

628 

2060 

500 

1640 

314 

1030 

197 

646 

40mA 

597 

1960 

472 

1550 

375 

1230 

236 

775 

148 

485 

50mA 

478 

1568 

378 

1240 

300 

984 

189 

620 

118 

388 

60mA 

296 

1300 

314 

1030 

250 

820 

157 

515 

98 

323 

70mA 

341 

1120 

270 

886 

214 

703 

135 

443 

84 

277 

80mA 

299 

980 

237 

775 

187 

615 

118 

388 

74 

243 

90mA 

264 

867 

209 

687 

166 

547 

105 

343 

66 

215 

100mA 

239 

784 

189 

620 

123 

492 

94 

310 

59 

194 

Table A-4: Total Auxiliary Power

Note:

The wire lengths indicated represent the one‐way distance between the source 
of power and the last detector in the branch. 

 

 