The proper use of wire and cable is necessary for the successful installation and operation of 
the LightSYS2 system. It is important to select wire of the correct thickness to minimize power 
loss and ensure reliable system operation. Take into account both the installationʹs current 
requirements and the wiring distances involved. The following tables provide useful 
information to help make your installation trouble‐free. 

AWG
Gauge
Size

Wire Diameter

Resistance:

Meters

Resistance: Feet

Millime
ters

Inches

Ω Per
Meter

Ω Per
100
Meters


Per
Foot

Ω Per
1000 Feet

24 

0.50 

0.020 

0.085 

8.5 

0.026 

26.0 

22 

0.64 

0.025 

0.052 

5.2 

0.016 

16.0 

20 

0.80 

0.031 

0.032 

3.2 

0.010 

10.0 

19 

0.90 

0.035 

0.026 

2.6 

0.008 

8.0 

18 

1.00 

0.040 

0.020 

2.0 

0.006 

6.0 

16 

1.27 

0.050 

0.013 

1.3 

0.004 

4.0 

14 

1.63 

0.064 

0.008 

0.82 

0.0025 

2.5 

Table A-1: Wire Facts

One-Way Wire Distance
Between LightSYS2
and Plug-In
Transformer

AWG (American Wire Gauge)
For best results use the indicated wire size
or larger (numerically lower) size

In Meters 

In Feet 

22 

20 

18 

16 

14 

Up to 5  

Up to 15  

 

 

 

 

 

5 ‐ 8  

15 ‐ 25  

 

 

 

 

 

8 ‐ 12  

25 ‐ 40  

 

 

 

 

 

12 ‐ 20  

40 ‐ 60  

 

 

 

 

 

20 ‐ 30  

60 ‐ 100  

 

 

 

 

 

Table A-2: Wiring Between the LightSYS2 Main Panel and the Plug-In Transformer