Page 153

Quick Keys

Parameter

Default

Range

MS Polling example
When selecting MS 1 (IP Only), MS 2 (IP only) and split report option 1

st

 

Backup 2

nd

 (using the default primary, secondary and backup time 

intervals), the report process will be as follows: 
In a normal state: 
Polling through the IP network using the IP module will occur every 30 
seconds according to the primary time interval to MS 1 and every 3600 
seconds (1 hour) according to the secondary time interval to MS 2. 
When communication to MS 1 fails, polling occurs every 30 seconds 
according to the backup interval to MS 2. When communication returns 
to MS 1, polling reverts back to the secondary time interval and occurs 
every 3600 seconds (1 hour) to MS#2 

Radio (LRT)

Quick Keys

Parameter

Default

Range

 

LRT (Long Range Transmission)

 

 

The LRT menu contains parameters for setting a system long‐range 
radio communication network, using the Location Aided Routing 
(LARS) protocol (LARS, LARS1, or LARS2) or E‐LINE protocol to 
facilitate detailed event transmission to monitoring stations.

 

Account

 

0–00FFFF 