Installer Programming

Page 79

Quick Keys

Parameter

Default

Range

 

 

24‐Hour Bypass  

 No

  

Yes/No

 

YES: It is possible for the user to bypass a 24‐hour zone. 
NO
: It is not possible for the user to bypass a 24‐hour zone. 

 

 

Technician Tamper  

 No

  

Yes/No

 

YES: It is necessary to enter the installer code to reset a tamper alarm (

). Therefore, resetting a tamper alarm requires the intervention of the 

alarm company. However, the system can still be armed although the 
tamper indication is on. 
NO
: Correcting the problem resets a tamper alarm, requiring no alarm 
company assistance. 

 

 

Technician Reset 

 No

  

Yes/No

 

YES: It is necessary to enter the installer code to reset an alarmed 
partition after it has been disarmed. This requires the intervention of the 
alarm company. 

Note

Before the Ready LED/ 

 can light., all zones within the partition must 

be secured. 
NO
: Once an alarmed partition is reset the Ready LED/

 lights when all 

zones are secured. 

 

Engineer Tamper   

 No

  

Yes/No

 

YES: After a tamper alarm, the system is not ready to arm and the tamper  

indication (

) LED is not restored. This requires the intervention of the 

alarm company. 
NO
: After a tamper alarm is restored the system is ready. 

 

Low Battery Arming  

 Yes

  

Yes/No

 

YES: Allows arming of the system when a low battery condition is 
detected (also in the Power Supply expansion module). 
NO: Arming the system is disabled when a low battery condition is 
detected. 

 

 

Bell 30/10  

 No

   

Yes/No

 

YES: Any internal sounders cease to sound for 10 seconds after each 30 
seconds of operation. 
NO
: Any internal sounders operate without interruption. 