Installer Programming

Page 106

 

 

Loop Response 

 

The Loop Response menu enables you to set the different times for 
which a zone violation must exist before the zone will trigger an alarm 
condition 

1) Normal: 400 ms (milliseconds). 

2) Long: 1 second 

3) Fast: 10 ms (milliseconds). 

4) Extra Fast:  1 ms (millisecond). This loop response is usually used 

for shutters or other devices that require very quick responses

Quick Keys

Parameter

Default

Range

  

 

Advanced 

  

  



 

ZZ 

Forced Arming 

  

  

This option enables or disables the use of forced arming for each of the 
systemʹs zones, as follows: 

1. If forced arming is enabled for a particular zone, it allows the system 

to be armed even though this zone is faulty. 

2. When a zone(s) enabled for forced arming is faulted, the red LED 

blinks during the disarm period. 

3. After arming, all zones enabled for forced arming are bypassed at 

the end of the exit delay time period (p. 70). 

4. If a faulted zone (one enabled for force arming) is secured during the 

armed period, it will no longer be bypassed and will be included 
among the systemʹs armed zones 





ZZ

Pulsed Counter 

   01

 

01‐15 

Specifies that the zone will count the number of open and close pulses 
received. If the zone exceeds the predefined number of pulses, the zone 
will be tripped and act according to its type definition. After a  25‐
second timeout the pulse counter is restarted. The pulse length is the 
currently defined loop response time period. (Refer to Zones: Loop 
Response, page 106.) 