First time, Manual clock adjustment by setting o4-17 to 1 – Yaskawa Z1000 AC Drive HVAC User Manual

Page 107

Advertising
background image

Verifying the New Time Setting

After pressing ENTER , the display will indicate “Entry accepted” and the new time value will be saved to the Real-Time

Clock (RTC).
If there is a problem with the entered time, the operator will indicate “Input error” and the screen will return to the time setting

display.

Canceling the Input

Pressing the ESC key will display “Aborted” on the operator, and no value will be saved to the RTC. Pressing OFF will abort

the setting process without any display, and no setting changes will be saved to the RTC.

Exiting from the Time Setting Screen Without Making Any Changes

If no changes are entered, the display will exit Real Time Clock Adjustment Display after a few seconds and no changes will

be saved.

n

Real-Time Clock Setting at Initial Power-up of a New Drive

Setting the Real-time clock is required at power-up of a new drive or after HOA keypad battery replacement.

Table 4.4

illustrates how to set the Real-Time Clock at initial power-up of a new drive.

Table 4.4 Clock Adjustment Procedure at Power-up of a New Drive

Procedure

Display

1

Turn the power on. The Real Time Clock Adjustment Display will appear. Use the right arrow

key to select the desired digit, then set the correct date and time using the up and down arrow

keys.

ALM

20

1

0/01/01 00:00

Second per month

+ 0 sec

YYYY/MM/DD HH:MM

ALM

2

After entering the Real-Time Clock data, press the ENTER key to save the changes.

The display will indicate “Entry Accepted” and return to the initial display in step 3 and the alarm

LED will be OFF.

ALM

Entry accepted

3

Initial display.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

DRV

Freq Ref (AI)

Rdy

FWD

LSEQ

LREF

n

Manual Clock Adjustment by Setting o4-17 to 1

The following actions are possible in the Clock Adjustment Mode:
• Set the current time
• Check the time set to the drive Real-Time Clock

Table 4.5

illustrates how to set the Real-Time Clock manually.

Table 4.5 Manual Clock Adjustment Procedure by Setting o4-17 to 1

Procedure

Display

1

The “Time Not Set” (TIM) display will appear if the Real-Time Clock data is not entered within

30 seconds of power-up on a new drive.

Refer to Fault Displays, Causes, and Possible

Solutions on page 198

for more details on the TIM display.

- MODE -

Time Not Set

RESET

DRV

ALM

TIM

FWD

ALM

2

Use the up and down arrow keys to scroll through display menu until the screen displays

“Programming”.

- MODE -

DATA

HELP

PRG

ALM

Programming

FWD

4.3 The Drive, Programming, and Clock Adjustment Modes

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

107

4

Start-Up Programming & Operation