Input signal selection for terminals a1 and a2, Terminal a2 input signal selection, Dip switch s1 – Yaskawa Z1000 AC Drive HVAC User Manual

Page 93: Refer to input, 10 control i/o connections

Advertising
background image

u

Input Signal Selection for Terminals A1 and A2

Terminals A1 and A2 can be used to input either a voltage or a current signal. Select the signal type using jumper S1 as

explained in

Table 3.10

. Set parameters H3-01 and H3-09 accordingly as shown in

Table 3.11

.

Note:

If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency

reference.

Table 3.10 Jumper S1 Settings

Terminal

Voltage Output

Current Output

Terminal A1

A2

A1

V

I

A2

A1

V

I

Terminal A2

A2

A1

V

I

A2

A1

V

I

Table 3.11 Parameters H3-01 and H3-09 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-01

Terminal A1 signal level selection

Selects the signal level for terminal A1.

0: 0 to 10 V with Zero Limit

1: 0 to 10 V without Zero Limit

2: 4 to 20 mA Current Input

3: 0 to 20 mA Current Input

0 to 3

0

H3-09

Terminal A2 signal level selection

Selects the signal level for terminal A2.

0: 0 to 10 V with Zero Limit

1: 0 to 10 V without Zero Limit

2: 4 to 20 mA Current Input

3: 0 to 20 mA Current Input

0 to 3

0

u

Terminal A2 Input Signal Selection

Terminal A2 can be used to input either a voltage or a current signal. Select the signal type using switch S1 as explained in

Table 3.10

. Set parameter H3-09 accordingly as shown in

Table 3.11

.

Note:

If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency

reference.

Table 3.12 DIP Switch S1 Settings

Setting

Description

V (left position)

Voltage input (-10 to +10 V or 0 to 10 V)

I (right position)

Current input (4 to 20 mA or 0 to 20 mA): default setting

Table 3.13 Parameter H3-09 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-09

Terminal A2 signal level selection

Selects the signal level for terminal A2.

0: 0 to 10 Vdc

1: -10 to 10 Vdc

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

2

3.10 Control I/O Connections

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

93

3

Electrical Installation