4.5 Powering Up the Drive

u

Powering Up the Drive and Operation Status Display

n

Powering Up the Drive

Review the following checklist before turning the power on.

Item to Check

Description

Power supply voltage

600 V class: Three-phase 500 to 600 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).
Check for proper grounding of drive and motor.

Drive output terminals and

motor terminals

Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.

Control circuit terminals

Check control circuit terminal connections.

Drive control terminal status

Open all control circuit terminals (off).

Status of the load and connected

machinery

Decouple the motor from the load.

n

Status Display

When the power supply to the drive is turned on, the HOA keypad lights will appear as follows:

Status

Name

Description

Normal

Operation

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-183

ALM

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

DRV

Freq Ref (AI)

Rdy

FWD

LSEQ

LREF

The data display area displays the frequency reference.

is lit.

Fault

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

ALM

- MODE -

EF3

Ext Fault S3

DRV

FWD

RESET

External fault (example)

Data displayed varies by the type of fault.

Refer to Fault Displays, Causes, and Possible

Solutions on page 198

for more information.

and

are lit.

4.5 Powering Up the Drive

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

117

4

Start-Up Programming & Operation