Enter data from the motor nameplate, 8 auto-tuning, Press to view the default setting – Yaskawa Z1000 AC Drive HVAC User Manual

Page 139: Press, And to enter the motor power nameplate data in kw, Press to save the setting

Advertising
background image

n

Enter Data from the Motor Nameplate

After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.

Note:

These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning”.

Step

Display/Result

1. Press

to access the motor output power parameter T1-02.

- A.TUNE -

T1-

02

= 0.75kW

(0.00 ~ 650.00)

PRG

Mtr Rated Power

Rdy

ESC

FWD

DATA

“0.75kW”

2. Press

to view the default setting.

- A.TUNE -

T1-02=

0

00.75kW

(0.00 ~ 650.00)

PRG

Mtr Rated Power

Rdy

FWD

“0.75kW”

3. Press

F1

left

,

F2

right

,

,

, and

to enter the motor power nameplate data in

kW.

- A.TUNE -

T1-02= 000.4

0

kW

(0.00 ~ 650.00)

PRG

Mtr Rated Power

Rdy

FWD

“0.75kW”

4. Press

to save the setting.

Entry Accepted

5. The display automatically returns to the display in Step 1.

- A.TUNE -

T1-

02

= 0.40kW

(0.00 ~ 650.00)

PRG

Mtr Rated Power

Rdy

ESC

FWD

DATA

“0.75kW”

6.

Repeat Steps 1 through 5 to set the following parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
• T1-05, Motor Base Frequency
• T1-06, Number of Motor Poles
• T1-07, Motor Base Frequency

- A.TUNE -

T1-

10

= X.XX Hz

(0.00 ~ 20.00)

PRG

Mtr Rated Slip

ESC

FWD

DATA

“X.XX Hz”

- A.TUNE -

T1-

03

= 200.0VAC

(0.0 ~ 255.0)

PRG

Rated Voltage

ESC

FWD

DATA

“200.0VAC”

Note:

To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.

4.8 Auto-Tuning

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

139

4

Start-Up Programming & Operation

Advertising