L8-05: input phase loss protection selection, L8-06: input phase loss detection level, L8-07: output phase loss protection selection – Yaskawa Z1000 AC Drive HVAC User Manual

Page 176

Advertising
background image

10 s

etc.

time

10 s

10 s

10 s

10 s

10 s

10 s

f

ref

× (L8-19)

f

ref

× (L8-19)

2

f

ref

× (L8-19)

4

f

ref

× (L8-19)

3

f

ref

Output frequency

Reset oH

Alarm

Reset oH

Alarm

Digital ouput (4D)

oH

Alarm

oH

Alarm

oH

Alarm

oH

Alarm

oH alarm number

Figure 4.36 Output Frequency Reduction During Overheat Alarm

n

L8-05: Input Phase Loss Protection Selection

Enables or disables the input phase loss detection.

No.

Name

Setting Range

Default

L8-05

Input Phase Loss Protection Selection

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

Enables input phase loss detection. Since measuring the DC bus ripple detects input phase loss, a power supply voltage

imbalance or main circuit capacitor deterioration may also trigger a phase loss fault (PF).
Detection is disabled if:
• The drive is decelerating.
• No Run command is active.
• Output current is less than or equal to 30% of the drive rated current.

n

L8-06: Input Phase Loss Detection Level

Sets the Input Phase Loss Detection (PF) Level.
Triggers PF fault when there is an imbalance larger than the value set to L8-06 in the drive input power voltage.
Detection Level = 100% = Voltage Class ×

No.

Name

Setting Range

Default

L8-06

Input Phase Loss Detection Level

0.0 to 25.0%

Determined by

o2-04

n

L8-07: Output Phase Loss Protection Selection

Enables or disables the output phase loss detection triggered when the output current falls below 5% of the drive rated current.

Note:

1. Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable

this parameter in such cases.

2. Output phase loss detection is not possible when the drive is running a PM motor with light load.

No.

Name

Setting Range

Default

L8-07

Output Phase Loss Protection Selection

0 to 2

1

4.13 Advanced Drive Setup Adjustments

176

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual